Adjustable Partition Support Pedestal: Setting Legs for 12–18 mm Panels
The leg is the least interesting part on the drawing and the one that decides whether a panel run stays square for the next decade. An adjustable partition support pedestal does three jobs at once: it carries the panel, it makes up for a floor that is never level, and it sets the headrail line that every door and lock depends on. Get the sequence wrong, and the error will surface two years later as a door that will not latch.
This is the installation logic we give contractors, in the order it should be done, plus the trap that shows up on almost every wet-area site.
What the pedestal is carrying
Do the rough numbers before choosing a model. A cubicle leg carries panel weight, the share of the headrail load, and any leaning load from someone using the partition as support. Typical panel weights, for orientation only:
| Panel type | Typical thickness | Approx. weight per m² | Leg load, 1.2 m × 2 m panel* |
|---|---|---|---|
| HPL compact laminate | 12–13 mm | 14–16 kg | ~17–20 kg |
| Particle board, HPL faced | 18 mm | 12–14 kg | ~15–18 kg |
| Solid phenolic core | 13 mm | 17–19 kg | ~21–24 kg |
| Glass-backed composite door | 18 mm | 20–25 kg | legs carry frame only |
*Rough figures for early sizing. For heavy panels, tall runs or public-assembly buildings, get the load checked by the project engineer rather than the hardware catalogue.
In practice most failures are not overload. They are loosening and corrosion, which is why the fixing and the material matter more than the nominal capacity.

Anatomy of an adjustable partition support pedestal
Four elements, and each has a failure mode:
- Base plate. Distributes load into the floor and takes the anchor. Too small a plate on a soft screed means the leg sinks under load.
- Threaded adjuster. The M-thread that gives you height range. This is where corrosion starts, because it is the part most likely to be left exposed.
- Clamp or head. Grips the panel edge. Must suit the actual panel thickness — our range covers 12–18 mm across 40+ models.
- Locking nut. Locks the height once set. Under-used on site, which is why legs drift.
The installation sequence that avoids later problems
Order matters more than technique.
- Survey the floor first. Take levels at every leg position, not just at the corners of the room. A 6 mm fall across a 3 m run is normal and must be absorbed by the legs, not by packing under the base plates.
- Establish the headrail line. Usually 1.9–2.1 m to the top of the panel, but confirm what the door hardware needs. Every subsequent height is measured from this line, not from the floor.
- Set the highest leg first, then work downhill. Start where the floor is highest, because a leg can be extended but not shortened below its minimum. This single rule prevents the classic problem of a run that runs out of thread at one end.
- Cut panels only after the legs are set. Panel cut lists produced from a nominal floor level are wrong on almost every site.
- Anchor as you go, not at the end. A run that is levelled but not anchored will move when the next trade leans on it.
- Lock every adjusting nut. Then check with a spirit level across three legs, not two.
Choosing the floor anchor by floor type
This is where installations quietly fail. The same expansion bolt behaves completely differently on four common floors.
| Floor type | Anchor that works | What fails |
|---|---|---|
| Structural concrete | Mechanical expansion bolt, correct embedment depth | Bolt too short, hits aggregate and spins |
| Screed on insulation (warm floor) | Longer anchor into the structural slab, or resin | Anchor holds the screed only; the screed crumbles |
| Tile on waterproofing membrane | Anchor through to substrate, seal the penetration | Membrane punctured — leak appears months later |
| Raised access floor | Through-bolt to the structural floor, or a spreader plate | Load sits on a 600 mm tile; the tile cracks |
The corrosion trap: exposed thread
Here is the failure we see most often, and it has nothing to do with load. The installer extends the leg 20 mm to meet an uneven floor, and the exposed thread sits in a washroom environment where it is mopped twice a day. If that thread is zinc plated, it corrodes within two years. Then the leg is permanently set, because the nut has seized.
The consequences are practical rather than cosmetic. When the panel run needs re-levelling — after a floor repair, after a leak, after the frame has settled — the contractor cannot adjust the legs and has to cut them out. A job that should have taken an hour becomes a partition rebuild.
Three ways to avoid it:
- Specify 304 stainless thread for any leg in a wet area or on a ground floor, not just for the visible parts.
- Keep the exposed thread covered — a shroud or a sleeve costs very little.
- Set the legs with the minimum extension needed, and take up the rest of the fall in the panel cut rather than in the thread.
Clamp range and the panel thickness question
A pedestal clamps an edge. If the clamp is specified for 12–13 mm and the panels arrive at 18 mm, nothing fits and somebody will “make it work” with a longer screw and no clamp engagement. On site this looks fine and behaves badly: the panel is held by friction and one screw, so it racks whenever a door is pulled hard.
Confirm the panel thickness from the actual delivery, not from the drawing. Panel suppliers substitute constructions more often than anyone expects. Our legs are built for 12–18 mm across more than 40 models, in stainless steel, zinc alloy, aluminium alloy and nylon, so the answer is a model change rather than a compromise — but the model has to be chosen against a real number.
Alignment tolerances worth holding
- Headrail line: within 2 mm over a 4 m run
- Plumb on each panel edge: within 1.5 mm over the panel height
- Leg-to-leg spacing: as designed, typically 1.0–1.5 m for a standard panel
- Floor clearance under doors: 12–20 mm, consistent across the run
Those are tighter than most sites hold by accident and looser than the eye notices. The reason to hold them is the door hardware downstream: a 3 mm drift in the frame is a lock that binds and a hinge that has to work harder every day.
Frequently asked
Do I need a leg on every panel?
Every vertical panel needs support at its free edge or at a junction. Whether that is one leg per panel, per junction, or a continuous floor channel depends on the system. What you cannot do is skip a leg in the middle of a run and rely on the headrail — the headrail is not designed to carry panel weight in bending.
Can I use plastic shims instead of adjusting the legs?
No. Shims compress, slide and rot, and they change the load path so the base plate is partly unsupported. If the leg’s range is not enough, the leg is the wrong model.
Are stainless legs worth the price difference?
In a wet area, almost always, for the same reason stainless hinges are: the failure you are buying protection against — a seized adjuster — costs far more to fix than the difference per leg. In a dry, low-traffic office washroom, zinc alloy with a good finish is a defensible choice.
What about floor-level drainage and cleaning?
Legs interrupt a mop pass and collect debris at the base plate. If the washroom is hosed down rather than mopped, specify a leg with a raised base and a smooth shroud so there is no ledge for water to sit on.